Electrical data |
Nominal voltage |
|
AC 24V, 50/60 Hz / DC 24V |
|
Power supply range |
|
AC/DC 19.2...28.8 V |
|
Power consumption |
Own consumption Dimensioning |
0.2 W Dependent on the actuator (see Technical data sheet for the actuator) |
|
Connection |
|
Spring terminals, max. 1.5 mm2 Max. 1 lead per terminal opening (cable ∅ 5 ... 10 mm, 4-core) Use a screwdriver to install |
|
Cable gland clamping range |
5 ... 10 mm |
|
Electrical isolation |
|
No |
Functional data |
Input impedance (U5 input) |
>100 k? |
|
Non-linearity |
|
<1% |
|
Control by controller (controller signal) |
Selectable with jumper: – Jumper set: 0 ... 20 mA → 0 ... 10 V (factory setting) – Jumper removed: 0 ... 20 mA → 0 ... 20 mA |
|
Load at 4…20 mA outlet |
0 ... 600 Ohm (signal conductor resistance + input resistance controller) |
Safety |
Protection class |
|
III Safety extra-low voltage |
|
Degree of protection |
|
IP66 |
|
EMC |
|
CE according to 2004/108/EC |
|
Mode of operation |
|
Type 1 |
|
Ambient temperature |
|
–30 … +50°C |
|
Non-operating temperature |
–40 … +80°C |
|
Ambient humidity range |
95% r.h., non-condensating |
|
Rated impulse voltage |
0.8 kV |
|
Control pollution degree |
3 |
|
Maintenance |
|
Maintenance-free |
Dimension / Weight |
Dimension |
|
See «Dimensions» on page 2 |
|
Weight |
|
Approx. 200 g |